Setting the switch points of an electric pressure switch for an application in the vacuum range isn’t a self-explanatory task. The next article therefore explains what needs to be taken into account with this setting. It involves a pressure switch with a hysteresis function. Instruments with this particular configuration are most frequently installed in industrial applications.
Electronic pressure switches, like the WIKA models PSD-4 and PSD-4-ECO or the A-1200 pressure sensor with IO-Link, operate as ?normally closed? or ?normally open?, depending on the task. The following graphics illustrate both switching functions with the respective switch and reset points:
In principle, the next applies: The switch point (SP) is higher than the reset point (RP) and the beginning of measuring range (MRS) is definitely smaller than the end of measuring range (MRE). This rule could be easily understood with settings for ambient air pressures.
Example: Control of a vacuum pump
On the other hand, setting the switch points in the vacuum range and therefore, ultimately, the switching function, requires more attention. To illustrate this, let?s take the control of vacuum pressure pump, for example, which must maintain vacuum pressure between -0.7 bar and -0.5 bar. For the task described, we select a pressure switch with a measuring selection of -1 ? 0 bar.
The start of measuring range (MRS) is therefore -1 bar, the end of measuring range (MRE) 0 bar. This means: At 0 bar (= start of operation) the switch ought to be closed, so as to switch on the vacuum pump. If the pressure drops to -0.7 bar, the switch must open and prevent the pump. When the pressure reaches the upper limit value of -0.5 bar, the pump should once again start and run until the pressure has again dropped to -0.7 bar.
ow must the switch points be set in this vacuum range? Let?s take the two pictures and translate MRS and MRE:
Here it is clear that the ?normally open? function must be selected, otherwise the pump would not activate. After entering the switch points, the schematic is obtained, which shows the way the pressure switch functions in accordance with the example:
Note
Information about WIKA?s electronic pressure switches can be found on the WIKA website. Do you want to buy pressure switches? Inside our WIKA online-shop you will discover some of our standard designs. In case you have any questions, your contact will gladly assist you to.
Also read our posts
What’s meant by the switching function ?hysteresis? with electronic pressure switches?
What is the difference between the switching functions ? Dejected ? and ?window? in pressure switches?
What’s meant by the ?normally open? switching function with pressure switches?